EFES Process Equipment Pvt. Ltd is a Customized Clean Room Solutions Provider.
We have a Comprehensive Understanding and Expertise in Executing Clean Room Solutions, Turnkey 1
HVAC and Clean Room Projects to Meet The Requirements and Intrinsic Regulations of Pharmaceutical and Biotechnological Industry.
EFESPRO Manufacturing Facilities Equipped with CNC Machinery, Top Class Powder Coating Line and High Pressure Foaming Machinery,
Enable EFESPRO to Meet the Divergent Requirements and Specifications of the Customers.
• Modular Clean Room Systems.
• Clean Room Equipments.
• HVAC Systems.
• Mechanical Piping and Utilities.
• Validations Services.
Material of Construction
PANEL ARE MADE WITH
GI POWDER COATED / SS 304 And GI PRE-COATRED.
SATINLESS STEEL SS 304 NO 04 FINISH WITH IN-FILL INSITU PUF,MINERAL WOOL , HONEYCOMB KRAFT PAPER
AND OTHER ACCESSORIES LIKE
• DYNAMIC & STATIC PASS BOX / TRANSFER HATCH
• VERTICAL & HORIZONTAL LAMINAR AIR FLOW UNIT
• MOBILE LAMINAR AIR FLOW (VERTICAL & HORIZONTAL AIR FLOW)
• REVERSE LAMINAR AIR FLOW (SAMPLING & DISPENSING BOOTH)
• GARMENT CUBICLES (DYNAMIC & STATIC)
• BIOSAFETY CABINT
• AIR SHOWER
• DEDUSTING TUNEEL (SS 304 & POWDER COATED MILD)
• DOOR INTERLOCKING SYSTEMS Etc.
Horizontal Laminar Air Flow Workstation
Laminar air Flow is localized clean air station to carry out various test under ISO
Class 5 (ISO std. 14644-1) filtered air. Horizontal Laminar Air Flow is used
when non toxic and nonflammable tests are carried out. Laminar Unit also consist
of UV light, UV hour meter, Steripot as per requirement. Sometimes antistatic
grill is provided to remove the static charge as per client requirement.
Std.Model |
Working Area (mm) (wxdxh) |
External Dimensions(wxdxh) |
Air Flow Velocity |
Air Cleanliness |
Air Flow Type |
HLAF-222 |
610x610x610 |
710x1150x1475 |
|
ISO CLASS-5 |
|
HLAF-322 |
915x610x610 |
1015x1150x1475 |
0.45±0.1 M/Sec |
(ISO 14644-1) |
Horizontal Air Flow Type |
HLAF-422 |
1220x610x610 |
1320x1150x1475 |
90±20 FPM |
CLASS-100 |
|
HLAF-622 |
1830x610 x610 |
1930x1150x1475 |
|
(US FED STD-209 E) |
|
TECHNICAL SPECIFICATIONS |
MOC |
1.2 mm thick CRCA Powder coated, or 1 mm thick SS -304 imported PVC coated sheet |
Pre-filter |
Pre-filter are made from Non-Woven HDPE mesh, Efficiency 95% down to 5 micron. |
Supply Filter |
Imported minipleat HEPA filter with hot melt technology, which confirms to EU-14 grade, Efficiency
rating 99.997% at 0.3 micron. |
Motor Blower Assembly |
EBM NADI, Dynamic Or Western Electric Make Blower Motor Assembly
1440 RPM, Single Phase, 230 V AC. |
Pressure Gauge |
Dwyer make pressure gauge- ( 0-50 mm/wg) |
Work Table |
SS 304,Work table |
DOP Port |
DOP Port at upstream of HEPA filter for HEPA integrity test. |
Electrical Supply |
230 V, Single Phase, 50 Hz, AC Supply. |
Vertical Laminar Air Flow Workstation
Vertical Laminar Air flow bench is used when air flow requirement is from
vertical fashion. It is used when toxic or flammable tests are carried out in
Laminar Air. Vertical air flow avoids direct throw of the air towards
operator’s face. Shutter is provided to avoid the air throw to the operator
face.
Std.Model |
Working Area(wxdxh) mm |
External Dimensions(wxdxh) mm |
Air Flow Velocity |
Air Cleanliness |
Air Flow Type |
VLAF-222 |
610x610x610 |
760x1260x1600 |
|
ISO CLASS-5 |
|
VLAF-322 |
915x610x610 |
1065x1260x1600 |
0.45±0.1 M/Sec |
(ISO 14644-1 ) |
Vertical Air Flow Type |
VLAF-422 |
1220x610x610 |
1370x1260x1600 |
90±20 FPM |
CLASS-100 |
|
VLAF-622 |
1830x610x610 |
2005x1260x1600 |
|
(US FED STD-209 E) |
|
TECHNICAL SPECIFICATIONS |
MOC |
1.2 CRCA Powder coated sheet or 1 mm thick SS- 304 imported PVC Coated sheet |
Pre-filter |
Pre-filter are made from Non-Woven HDPE mesh, Efficiency 95% down to 5 micron. |
Supply Filter |
Imported minipleat HEPA filter with hot melt technology, which confirms to EU-14 grade, Efficiency
rating 99.997% at 0.3 micron. |
Motor Blower Assembly |
Statically and dynamically balanced blower motor assembly, EBM NADI ,Dynamic ,Western Electric or
equivalent make to take care of sufficient amount of static pressure and air flow requirement.
1440 RPM, Single Phase, 230 V, 50Hz ,AC. |
Pressure Gauge |
Dwyer make pressure gauge- ( 0-50 mm/wg) |
Work Table |
SS 304,Work table |
DOP Port |
DOP Port at upstream of HEPA filter for HEPA integrity test. |
Electrical Supply |
230 V, Single Phase, 50 Hz, AC Supply. |
OPTIONAL ACCESSORIES
1. UV light with hour meter 2. SS 304 Gas cock for Gas and Air
3. Variable Speed Control 4. Flame proof fitting
Reverse Laminar Air Flow (Sampling/ Dispensing Booth)
Reverse Laminar Air Flow(RLAF) is used to control the hazardous emissions of powder
dust during powder dispensing/sampling processes without any risk to operator and
products as well protecting the environment. The downdraught of HEPA filtered air
prevents airborne dust caused by handling operation away from the operator
breathing zone. Three levels of air filtration is carried out into the booth air stream.
Primary filtration at 10 micron, Intermediate filtration at 5 micron and final filtration
at 0.3 micron through Mini pleat HEPA filter. Exhaust through mini-pleat HEPA filter at
top of the unit.
Std.Model |
Working Area(wxdxh) mm |
External Dimensions(wxdxh) mm |
Air Flow Velocity |
Air Cleanliness |
RLAF-43 |
1315x1065x1830 |
1395x1660x2200 |
|
ISO-5 (ISO 14644-1) |
RLAF-44 |
1315x1340x1830 |
1395x1965x2200 |
0.45 ± 0.1 M/Sec |
Class-100 |
RLAF-64 |
1950x1340x1830 |
2030x1965x2200 |
90± 20 FPM |
(FED STD 209 E) |
TECHNICAL SPECIFICATIONS |
MOC |
Imported PVC Coated SS 304, 1 mm thick |
Pre-filter |
Non woven synthetic with HDPE mesh, EU-4 Grade with an efficiency rating better than90% at 10 micron. |
Intermediate Filter |
Made from non woven synthetic with HDPE mesh, EU-5 Grade with an
efficiency rating better than 95% at 5 micron. |
Supply Filter |
Imported minipleat HEPA filter with hot melt technology, EU-14 Grade
with an efficiency rating better than 99.997% for 0.3 micron. |
Exhaust Filter |
Minipleat HEPA filter with hot melt technology, EU-14 Grade at exhaust
with efficiency rating of 99.997% at 0.3 micron. |
Motor Blower |
EBM NADI, Dynamic, Western Electric make, 1440 RPM,1 Phase, 230V,
50Hz, AC. |
Pressure Gauge |
Dwyer Make Magnehelic pressure gauge. |
DOP Port |
DOP Port at upstream of HEPA for filter integrity test.. |
Power Supply |
230V, 1 Phase, 50 Hz, AC Supply. |
Vertical Laminar Air Flow (Ceiling Suspended Type Or Stand Mounted Type)
Vertical Laminar Air Flow unit draws air in through the top or side of the
unit through pre-filter ,through a plenum and vertically down over the
work surface and past the lap of the operator. It has the advantage of not
passing air towards the face of the operator. It is used for work with low
risk substances with protection of working material from environment.
MS CRCA or SS 304 perforated grill or CG screen is provided at filter
face as per requirement. It is used as OT Plenum also.
Std.Model |
HEPA Filter Area wxd (mm) |
External Dimensions(wxdxh) mm |
Air Flow Velocity |
Air Cleanliness |
CSVLAF-322 |
915x610 |
1065x760x650 |
|
ISO-5 |
CSVLAF-422 |
1220x610 |
1370x760x650 |
0.45 ± 0.1 M/Sec |
(ISO-14644-1) |
SMVLAF-322 |
915x610 |
1065x760x650 |
90± 20 FPM |
Class-100 |
SMVLAF-422 |
1220x610 |
1370x760x650 |
|
(FED Std 209E) |
TECHNICAL SPECIFICATIONS |
MOC |
CRCA Power coated 1.2 mm thick sheet or SS 304 1 mm thick sheet |
Pre-filter |
Made from Non-Woven synthetic HDPE mesh, EU-5 Grade with an efficiency rating
95% at 5 micron. |
Supply HEPA Filter |
Imported minipleat HEPA filter with hot melt technology, EU-14 Grade with
efficiency rating better than 99.997% at 0.3 micron. |
Motor Blower Assembly |
Statically and dynamically balanced blower motor EBM NADI, Western Electric,
Dynamic make,1440 RPM, 1 Phase, 230V, AC. |
Pressure Gauge |
Dwyer make magnehelic pressure gauge. ( 0-50mm/wg). |
DOP Port |
DOP Port or filter integrity test is provided at upstream of HEPA. |
Noise Level |
Less than 67 d B. |
Power Supply |
230 V, 1 Phase, 50 Hz, AC. |
OPTIONAL ACCESSORIES
1.PVC Vinyl curtains 2. Variable Speed 3. UV light 4. Flame Proof fittings
Fan Filter unit (FFU) is a leading edge FFU unit designed to provide filtered laminar air flow over a specific
area. The unit integrates a high efficiency fan together with a HEPA/ ULPA filter. The FFU draws in
contaminated air from top of the module and exhausts filtered clean air vertically class 100 to class 100000
clean rooms. (as per US Federal Standard 209 E or ISO-Class 5- ISO Standard 14644-1 ).
Std.Model |
Working Area(w x d) mm |
External Dimensions(wxdxh) mm |
Air Flow Velocity |
Air Flow Type |
Air Cleanliness |
FFU-221 |
570x570 |
575x575x286 |
0.45±0.1M/Sec |
|
ISO-Class 5
(ISO 14644-1) |
FFU-421 |
1170x570 |
1175x575x303 |
90±20 FPM |
Vertical Air Flow Type |
Class 100 |
FFU-441 |
1170x1170 |
1175x1175x333 |
|
|
(FED Std 209E) |
TECHNICAL SPECIFICATIONS |
MOC |
1.2 mm CRCA Powder coated or SS 304 1mm thick sheet. |
Pre-filter |
F5- filter , Efficiency 95% at 5 Micron. |
Supply Filter |
HEPA (H13/H14) Or ULPA (U15/U16). |
Blower Motor |
Backward curve radial fan, Airtech Japan make. |
Blower Static |
23-24 mm/wg. |
Features |
LED on filter face to show operation status. |
Power Supply |
230V, 1 Phase, 50 Hz, AC. |
Mobile Laminar Air Flows are used for transportation of the sterile products
inside the ISO(14644-1) Class 5, ( FED Std 209 E Class 100) particle free
work area to ensure that the contamination free transportation is carried out.
The working area is under positive pressure class 100 filtered area hence
avoids contamination. Battery back up is provided to maintain air flow
continuity during transportation. Side vinyl curtains or acrylic sheet is
provided as per requirement.
Std.Model |
Working Area (wxdxh) mm |
External Dimensions(wxdxh) mm |
Air Flow Velocity |
Air Cleanliness |
MLAF-322 |
915x610x610 |
1065x760x2050 |
0.45±0.1 M/sec |
ISO-Class-5 |
MLAF-422 |
1220x610x610 |
1370x760x2050 |
90±20 FPM |
(ISO 14644-1) |
MLAF-522 |
1525x610x610 |
1675x760x2050 |
|
Class-100 |
MLAF-622 |
1830x610x610 |
2005x760x2050 |
|
(FED Std- 209 E) |
TECHNICAL SPECIFICATIONS |
MOC |
1 mm thick SS 304, Imported PVC coated sheet. |
Pre-filter |
Made from Non-woven synthetic with HDPE Mesh, EU-5 Grade with an efficiency
95% at 5 micron. |
Supply Filter |
Imported minipleat HEPA filter with hot melt technology which confirms to H-14
Grade at supply position with an efficiency of 99.997% at 0.3 μ. |
Motor Blower |
Statically and dynamically balanced blower motor of EBM NADI, Dynamic or Western
Electric, 1440 RPM, 1 Phase, 230V, 50 Hz, AC. |
Pressure Gauge |
Dwyer make pressure gauge. ( 0-50 mm.wg). |
DOP Port |
DOP Port for HEPA integrity test. |
Castor Wheels |
PU Coated lockable castor wheels. |
Battery Back-up |
Battery back- up with inverter for 30 minutes. |
Vinyl curtains |
Four side PVC vinyl curtains as per requirement.. |
Power Supply |
230V, 1 Phase, 50 HZ ,AC. |
OPTIONAL ACCESSORIES
1.PVC Vinyl curtains 2. Variable Speed 3. UV light 4. Flame Proof fittings
Bio-safety cabinet is used to protect product, personnel and environment.
Mostly it is used when risky microorganisms are handled. Most widely used
Bio- Safety Cabinet are of class-II type A2and B2. Class-II A2 type Bio-Safety
cabinet have partial exhaust i.e. 30% and Class-II-B2 cabinet have 100%
exhaust. Type-II B2 cabinet is used when most toxic or radioactive substances
are handled..
Std.Model |
Working Area (wxdxh) mm |
External Dimensions(wxdxh) mm |
Air Flow Velocity |
Air Cleanliness |
BSC-322 (II A2/B2) |
915x610x610 |
1105x1050x2130 |
0.45 ± 0.1 M/sec |
ISO-Class-5 |
BSC-422(II A2/B2) |
1220x610x610 |
1410x1050x2130 |
|
(ISO STD- 14644-1) |
BSC-622(II A2/B2) |
1820x610x610 |
2010x1050x2130 |
90 ± 20 FPM |
Class-100 (FED 209 E) |
TECHNICAL SPECIFICATIONS |
MOC |
1.2 mm CRCA Powder coated Or SS 304 1mm thick sheet. |
Pre-filter |
Made from non-woven synthetic with HDPE Mesh, EU-5 Grade,With an
efficiency of 95% at 5 Micron. |
Supply Filter |
Minipleat HEPA filter with hot melt technology, EU-14 Grade, Efficiency
99.997% at 0.3 micron. |
Exhaust Filter |
Minipleat HEPA fIlter with hot melt technology, EU-14 Grade, Efficiency
rating of 99.997% for 0.3 micron. |
Motor Blower |
EBM NADI, Dynamic, Western Electric make, 1440 RPM, 1 Phase, 230V, 50
Hz, AC. |
Pressure Gauge |
Dwyer make magnehelic pressure gauge. |
Door Opening Alarm |
Excessive door opening alarm. |
Work Table |
SS 304 Work table with front and back side perforation for cleaning. |
Exhaust Duct |
SS 304, 1 Feet long Elbow duct for exhaust. |
Vinyl curtains |
Four side PVC vinyl curtains as per requirement.. |
Power Supply |
230 V, 1 Phase, 50 Hz, AC supply. |
Positive Pressure Module is designed to maintain positive pressure inside work
area. It is wall mounted type or Ceiling suspended type. It is of having capacities
of 150 CFM to 1500 CFM. Larger modules are normally used in production area.
The smaller units are used to reduce biological and non biological airborne
particulate activity in microbiological laboratories and intensive care units..
Std.Model |
Working Area (wxdxh) mm |
External Dimensions(wxdxh) mm |
Air Flow Velocity |
Air Cleanliness |
PPU-A |
610x610 |
760x760x750 mm |
0.45 ± 0.1 M/sec 90 ± 20 FPM |
ISO-Class-5 |
PPU-B |
610x1220 |
760x1370x750 mm |
|
(ISO STD- 14644-1) |
TECHNICAL SPECIFICATIONS |
MOC |
1.2mm thick CRCA Powder coated Or SS 304, 1mm thick PVC coated sheet. |
Pre-filter |
Made from non-woven synthetic with HDPE Mesh, EU-5 Grade,With an
efficiency of 95% at 5 Micron. |
Supply Filter |
Minipleat HEPA filter with hot melt technology, EU-14 Grade, Efficiency
99.997% at 0.3 micron. |
Motor Blower |
EBM NADI, Dynamic, Western Electric make, 1440 RPM, 1 Phase, 230V, 50 Hz,
AC. |
Pressure Gauge |
Dwyer make magnehelic pressure gauge. |
Perforated HEPA Grill |
Capsule perforated grill at filter face to protect HEPA filter. |
ON/ OFF Switch |
ON/OFF Switch with power on indication on front side of the unit. |
Power Supply |
230 V, 1 Phase, 50 Hz, AC supply. |
Air showers are used at entrance of dust free premises. High velocity clean air
bath is created inside air shower chamber to remove dust particles from human
body ,clothes and material if carried out through the air shower. It is a barrier by
door interlocking between internal & external environment to avoid the dust. It
is used as recovery unit also in gold industry. Gold dust trapped in HEPA filter is
recovered by burning the HEPA filter.
Std.Model |
Working Area (wxdxh) mm |
External Dimensions(wxdxh) mm |
Persons |
Velocity |
Air Cleanliness |
AS-TE-1000 |
800x900x1900 |
1700x1000x2200 |
1 to 2 |
25to30 (M/Sec) |
ISO-Class 5 (ISO- 14644-1) |
AS-SE-1000 |
800x1900x1900 |
1700x2000x2200 |
1 to2 |
4900 to 5900 (FPM) |
Class 100 (FED Std 209E) |
AS-TE-2000 |
800x1900x1900 |
1700x2000x2200 |
3 to 4 |
|
|
AS -TE -3000 |
800x2900x1900 |
1700x3000x2200 |
5 to 6 |
|
|
AS-TE-TB-1000 |
800x900x1800 |
1300x1000x2500 |
1 to 2 |
|
|
AS-TE-TB-2000 |
800x1900x1800 |
1300x2000x2500 |
3 to 4 |
|
|
AS-TE-TB-3000 |
800x2900x1900 |
1300x3000x2500 |
5 to 6 |
|
|
TECHNICAL SPECIFICATIONS |
MOC |
1.2 mm thick CRCA Powder coated or SS- 304 1mm thick imported PVC coated sheet. |
Pre-filter |
Pre-filter are made from Non-Woven HDPE mesh, Efficiency 95% down to 5 micron. |
Supply Filter |
Imported minipleat HEPA filter with hot melt technology, which confirms to EU-14 grade,
Efficiency rating 99.997% at 0.3 micron. |
Motor Blower Assembly |
Statically and dynamically balanced blower motor assembly, Hindusthan or equivalent make to
take care of sufficient amount of static pressure and air flow requirement.
2800 RPM, Three Phase, 440 V ,50Hz ,AC. |
Pressure Gauge |
Dwyer make pressure gauge- ( 0-100 mm/wg). |
Control System |
Interlocking system to ensure that both the doors will not open at the same time. Both the doors
locked during operation of the air shower. Time adjusted from 30 sec to 5 Minutes. |
DOP Port |
DOP Port at upstream of HEPA filter for HEPA integrity test.. |
Electrical Supply |
230 V, Single Phase, 50 Hz, AC / 415 V , Three Phase, 50 Hz AC supply. |
Noise Level |
Below 67 dB |
Air mist shower is a contamination control equipment for the respiratory
protection from inhalation hazards to the operator during de-gowning process.
When person removes his/her protective clothing he/she also removes primary
personal protection (respirator ) . The mist air shower is used to reduce the
possible deposition of the particulate in the operators breathing zone. Air mist
shower also reduces contamination in de-gowning area. Air mist shower works by
wetting the surface of operators gowning with fine mist causing the powder to
stick the gowning surface instead of becoming airborne contamination.
Std.Model |
Working Area (wxdxh) mm |
External Dimensions(wxdxh) mm |
Persons |
AMS-TE-1000 |
800x900x1900 |
1700x1000x2200 |
1 |
AMS-TE-2000 |
800x1900x1900 |
1700x2000x2200 |
2-3 |
AMS-TE-3000 |
800x2900x1900 |
1700x3000x2200 |
3-4 |
TECHNICAL SPECIFICATIONS |
MOC |
SS 304 mat finish, 19 SWG (1mm thick) PVC Coated sheet. |
Supply Mist |
Supply mist through SS 304, SS Nozzles with settable time. Solenoid valve at entry junction.
Compressed air through compressor to be provided by client. |
Drain Outlet |
Internal inclined sheet provided for drain outlet. |
Mist Jet System |
Nozzle arrangement is such that it covers total body at 4 bar pressure. Total nozzles -9 Nos
( 4 nozzles at right side, 4 nozzles at left side and 1 nozzle at top side). |
Water Line |
Proper water line by using Aeroflex / SM & N tube, Valves and sealants with avoiding leakages through
pipeline and nozzles. |
Doors |
SS 304, PUF insulated with view window , door closer ( Dorma make), handles and hinges
Interlocking for Entry and Exit doors. Automatic door interlocking system along with electromagnets. |
Electricals |
Operation through sequential logic controller, ON /OFF switches for operating tube light and
Auxiliary sockets, Fluorescent light 500 Lux. |
Power supply |
3 core connection cable along with 6/16 Amp. 3 pin top, 3 mtrs long cable
230V , 1 phase 50 Hz supply. |
Buyers Scope |
Water supply at 2 to 3 Kg/cm2 and air supply 4 to 6 Kg/cm2 is in buyers scope |
Specially designed garment cabinet provides a wash of sterile filtered clean
air through HEPA filters. The cabinet protects dust and other particulates
on clean room garments or other material. It is kept in change room to
store the garments. It is of vertical air flow type or horizontal air flow type
depending upon the requirement. Sometimes heater is also provided to
dry the wet garments to avoid sweating odor from the garments.
Std.Model |
Internal Size(wxdxh)mm |
External Size(wxdxh)mm |
Air Velocity |
Air Cleanliness |
GSC-226 |
610x610x900 |
760x760x1800 |
0.45±0.1 ISO |
Class-5 |
GSC-326 |
915x610x900 |
1065x760x1800 |
M/Sec FED Std |
|
GSC-426 |
1220x610x900 |
1370x760x1800 |
90±20FPM |
Class-100 |
TECHNICAL SPECIFICATIONS |
MOC |
1.2 mm thick CRCA Powder coated or SS 304 1mm thick imported PVC Coated sheet. |
Prefilter |
Made from Non-Woven synthetic HDPE mesh, EU-5 Grade with an efficiency
rating 95% at 5 micron. |
Supply HEPA filter |
Imported minipleat HEPA filter with hot melt technology, EU-14 Grade with
efficiency rating better than 99.997% at 0.3 micron. |
Fresh Air Filter |
Non woven synthetic with HDPE mesh filter, EU-4 Grade, 90% efficiency at 10
micron provided |
Motor Blower Assembly |
Statically and dynamically balanced blower motor EBM NADI, Western Electric,
Dynamic make,1440 RPM, 1 Phase, 230V, AC |
Pressure Gauge |
Dwyer make magnehelic pressure gauge. ( 0-50mm/wg). |
DOP |
Port DOP Port or filter integrity test is provided at upstream of HEPA. |
Noise |
Level Less than 67 d B |
UV light |
UV light for germ killing is provided. |
Interlock |
Electromagnetic interlock between door and UV provided |
Hanging |
SS 304 hanging arrangement or removable shelves or hangers |
Power Supply |
230 V, 1 Phase, 50 Hz, AC. |
Personnel traffic is the most important factor which must be controlled.
Pass boxes allows material to be transferred without actual personnel
movement. Freudenberg Static pass boxes are used when material
movement is inside the classified area’s. Pass boxes are provided with
door interlocking system to avoid contamination. Inside pencil coving is
provided to avoid dust deposition in the pass box working area.
Std.Model |
Internal Size(wxdxh)mm |
External Size(wxdxh)mm |
Power Supply Required |
SPB-222 |
600x600x600 |
740x670x750 |
|
SPB-333 |
900x900x900 |
1040x970x1050 |
230 V, 1Phase, 50 Hz |
SPB-444 |
1200x1200x1200 |
1340x1270x1350 |
AC Supply |
TECHNICAL SPECIFICATIONS |
MOC |
1.2 mm thick CRCA Powder coated, or SS 304 1mm thick imported PVC Coated sheet. |
Door Construction |
Double skinned door construction. |
Door Interlocking |
Electromagnetic Interlocking type door arrangement. |
Door release switch |
Door release switch provided on both the sides |
Internal Coving |
Internal pencil coving is provided |
OPTIONAL ACCESSORIES:
1.Mechanical door interlocking of Pass Box
2.UV light with UV Hour meter and interlocking of UV light with pass box doors. When pass
box door is opened the UV light will blow off and Fluorescent light will blow on.
3.Flange for sealing the gaps in between the wall or panels and pass box external skin.
4. Floor mounted construction.
5. Stand for pass box support.
6. Door drop seal.
7. Flame proof fitting of pass boxes.
8. Rigid floor support when heavy material movement is considered.
Dynamic pass boxes are used to transfer the material through controlled
environment without much personnel movement. It avoids cross
contamination during transfer of the material. Pass boxes are available with
some standard dimensions but it is manufactured as per customized
requirement also. Filtered HEPA air is provided inside the pass box to avoid
contamination. UV light and Florescent light is also provided in dynamic pass
boxes.
Std.Model |
Working Area (wxdxh) mm |
Overall Dimensions (wxdxh) mm |
Air Flow |
Air Cleanliness |
DPB-222 |
600x600x600 |
740x670x1240 |
0.45 ± 0.1 M/S |
ISO- Class-5 (ISO 14644-1) |
DPB-333 |
900x900x900 |
1040x970x1540 |
90 ± 20 FPM |
Class-100 (US FED 209 E) |
DPB-444 |
1200X1200X1200 |
1340x1270x1840 |
|
|
TECHNICAL SPECIFICATIONS |
MOC |
1.2 mm CRCA Powder coated or SS 304, 1mm thick imported PVC Coated sheet. |
Pre-Filter |
Non woven synthetic with HDPE mesh, Confirms to EU-5 Grade with an efficiency rating better
than 95% at 5 micron. |
HEPA filter |
Minipleat HEPA filter with Hot melt technology, which confirms to EU-14 Grade . Efficiency
99.997% at 0.3 micron level. |
Motor Blower |
Statically or Dynamically balanced blower motor assembly EBM NADI, Dynamic or Western electric
make or equivalent. 1440 RPM, 1 Phase, 230 V, 50 Hz Ac. |
Pressure Gauge |
Dwyer make pressure gauge. (0.50mm/wg). |
Interlocking |
Electromagnetic Interlocking. |
SS Coving |
SS Pencil coning inside pass box. |
DOP |
DOP Port provided for filter integrity test. |
Power Supply |
230V, 1 Phase, 50 Hz, AC Power supply. |
OPTIONAL ACCESSORIES :
1.UV light with UV hour meter
2. Mechanical Interlocking
3. Door Drop Seal
4.Audio Visual Alarm
5.Flame Proof fittings
#634, 3rd cross, HMT layout,
Ganganagar, R T Nagar, Bangalore-560032.
Karnataka State, INDIA.
+91 98450 68437
skr@techmach.in
sales@techmach.in